10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.
The AIPE exam has 80 questions and runs 2 hours 30 minutes.
These 10 free AIPE questions are organized by exam domain, so you can see how each part of the Accessibility Inspector/Plans Examiner blueprint is tested. Reveal the answer and explanation under each question.
Domain 1: General Administrative and Scoping Provisions
Question 1
An existing store's primary-function sales-area alteration costs $120,000, including $3,000 to correct an altered doorway. A separate $30,000 roof repair does not affect the primary-function area. Supporting accessible-route improvements would cost $36,000. The disproportionate-cost provision applies to that supporting work. Under the 2024 IEBC, which allocation correctly distinguishes the two accessibility obligations?
Show answer & explanation
Correct answer: C - Use a $24,000 route allowance; the doorway correction remains part of the altered-area work.
Domain 2: Building Blocks
Question 2
A new public toilet-room detail shows a 70-inch-diameter turning circle with a 14-inch-deep segment beneath the lavatory on one side. Compliant knee and toe clearance is available throughout that segment. When reviewing the overlap shown, which limitation should the plans examiner apply under ICC A117.1-2017?
Show answer & explanation
Correct answer: A - The circle may overlap the knee and toe space by no more than 10 inches.
Domain 3: Accessibility Routes
Question 3
On the push side of a manual office door, the front-approach clearance is 54 inches deep and extends 8 inches beyond the latch side. This is new construction, and the door has both a closer and a latch. Its clear opening is 33 inches; its 3/8-inch threshold is beveled at 1:2. Which revision resolves the accessibility defect under ICC A117.1-2017?
Show answer & explanation
Correct answer: C - Increase the latch-side clearance from 8 to 14 inches.
Question 4
During review of a new three-story Group B office, the designer deletes two-way communication at the accessible upper-floor passenger-elevator landings because the building is sprinklered throughout under IBC Section 903.3.1.1. The stairs qualify for the area-of-refuge exception. There are no ramps to the discharge level or separate refuge communication systems. The elevator is not designated for accessible egress. What does the 2024 IBC require?
Show answer & explanation
Correct answer: A - Provide two-way communication at the upper-floor elevator landings.
Question 5
Field measurements of an exterior accessible walkway show a 1:24 running slope, a 1:40 cross slope, and 54 inches of clear width. The contractor offers to add ramp handrails rather than regrade the pavement. Which proposed correction addresses the slope violation under ICC A117.1-2017?
Show answer & explanation
Correct answer: C - Reduce the cross slope to 1:60 while retaining the running slope.
Domain 4: General Site and Building Elements
Question 6
Two separate parking facilities serve an office campus: one has 180 spaces and the other has 40. Accessible spaces will be provided within each lot, and neither lot serves a use subject to a special parking percentage. Applying the 2024 IBC requirements to each facility, what is the combined minimum provision?
Show answer & explanation
Correct answer: D - 8 accessible spaces in total, including 2 van-accessible spaces.
Domain 5: Plumbing Elements and Facilities
Question 7
A designated wheelchair-accessible toilet compartment contains a floor-mounted water closet with its centerline 19 inches from the side wall and its seat 18 inches above the floor. The compartment is 61 inches wide and 60 inches deep. The installer cites a 17-to-19-inch centerline range. Which response correctly applies ICC A117.1-2017?
Show answer & explanation
Correct answer: B - Move the centerline to 17 inches; the cited range applies to ambulatory compartments.
Domain 6: Communication Elements
Question 8
Beside an outward-swinging toilet-room door, a tactile identification sign has compliant characters and Braille, with tactile character baselines 50 to 58 inches above the floor. It is on the latch-side wall. Its centered 18-by-18-inch reading area is crossed by the door when opened 30 degrees. Which aspect of this installation fails ICC A117.1-2017?
Show answer & explanation
Correct answer: C - The door crosses the required reading area before reaching 45 degrees.
Domain 7: Special Rooms and Spaces
Question 9
Two adjacent wheelchair spaces in a new theater are each 34 inches wide and 54 inches deep. Each has direct side entry from an accessible aisle; fixed construction prevents front or rear entry. The companion seats and circulation paths comply. Which replacement dimensions for each wheelchair space satisfy ICC A117.1-2017 without changing the entry arrangement?
Show answer & explanation
Correct answer: B - 34 inches wide by 62 inches deep.
Domain 9: Dwellings and Sleeping Units
Question 10
At final inspection of a Type A apartment, a base cabinet remains below the accessible kitchen sink. Its removal would not disturb the countertop, sink, or plumbing and would expose the required knee and toe clearance. The floor beneath and wall behind are finished, the sink is at a compliant height, and exposed pipes are protected. How should the cabinet be treated under ICC A117.1-2017?
Show answer & explanation
Correct answer: D - Permit the removable cabinet as an adaptable Type A feature.